The electrical tester is designed for insulation measurements with a test voltage of up to 15 kV. The measuring range from 0 ... 30 TΩ and other measuring functions make the tester versatile. With 4 quick selection buttons for common test voltages and the option of setting the voltage in 500 V steps. Pre-configured diagnostic tests, including (PI), dielectric absorption ratio (DAR) and a memory function for 200 measurements. These can be transferred to the software via the interface, which also enables the insulation measuring device to be operated. The electrical tester can also be used to measure AC and DC voltages up to 600 V. The electrical tester is supplied in a robust case that offers IP66 protection even when the lid is closed.
In the course of its normal service life, electrical insulation is exposed to various stresses that lead to its deterioration. This is caused by thermal, mechanical and chemical influences as well as moisture. Although the insulation is designed to withstand these stresses over many years, abnormal stresses can intensify the natural ageing process and drastically shorten the service life. It is therefore advisable to regularly check whether an accelerated ageing process is taking place and, if necessary, to determine whether the effects are reversible.
Electrical Tester PCE-IT 150
- 15 kV insulation tester
- Insulation resistance up to 30 TΩ
- Polarisation index PI
- Dielectric absorption ratio DAR
- 4 buttons for test voltage
- Memory for 200 measured values
- incl. software
Direct voltage DC Measuring range 30 V ... 600 V Resolution 1 V Accuracy ±(2.0% v.Mw. +3 digits) AC voltage AC Measuring range 30 V ... 600 V Resolution 1 V Accuracy ±(2.0% v.Mw. +3 digits) Insulation resistance Measuring range 0 GΩ ... 1 GΩ Resolution 0.001 GΩ Accuracy ±(5% v.Mw.+5 digits) Insulation resistance Measuring range 1 GΩ ... 10 GΩ Resolution 0.01 GΩ Accuracy ±(5% v.Mw.+5 digits) Insulation resistance Measuring range 10 GΩ ... 100 GΩ Resolution 0.1 GΩ Accuracy ±(5% v.Mw.+5 digits) Insulation resistance Measuring range 100 GΩ ... 1 TΩ Resolution 1 GΩ Accuracy ±(5% v.Mw.+5 digits) Insulation resistance Measuring range 1 TΩ ... 10 TΩ Resolution 10 GΩ Accuracy ±20% Insulation resistance Measuring range 10 TΩ ... 30 TΩ Resolution 100 GΩ Accuracy ±20% General technical data Measurement functions HOLD, PI, DAR Display type LCD Memory medium Internal memory Memory capacity 200 measurements Interface RS232 Automatic switch-off 5 min Automatic switch-off can be deactivated no Test voltage 500 V ... 15 kV Safety standard CAT IV 600 V Menu language English Protection class (device) IP66 Protection class (additional information) Only with closed lid Power supply 100 ... 240 V | 50/60 Hz Plug type Euro plug device Weight 6362 g Dimensions (L x W x H) 325 x 430 x 132 mm Operating conditions 0 ... 40 °C , 0 ... 80 % r.H Storage conditions 0 ... 40 °C , 0 ... 80 % r.H Capacity 5200 mAh